RCBO Keeps Tripping? Causes and What to Do

Jeremy HurstReviewed byJeremy Hurst, Founder

Newer fuse boards often have a separate switch with its own test button for every circuit. These are RCBOs. When one trips, only that circuit goes off, which makes the fault easier to find than on an old board. This guide explains why an RCBO trips, a safe check you can do yourself, and the faults we find most often, including the one that catches people out after a new consumer unit.

What is an RCBO?

An RCBO (residual current breaker with overcurrent protection) does two jobs in one switch:

  • Earth leakage protection, like an RCD. It trips if current leaks to earth, for example through water, a faulty appliance or a person.
  • Overload and short-circuit protection, like an MCB. It trips if the circuit draws more current than it’s rated for, or if live touches neutral.

So when an RCBO trips, the first question is which of the two jobs made it trip. Some RCBOs show this with a coloured flag or indicator on the front. Many don’t, so the pattern of the trip is the best clue. If your board has one or two big RCD switches covering lots of circuits instead, read what to do when your RCD trips.

Overload or earth leakage? Reading the clues

It trips when lots of things are on. For example, the kettle, microwave and toaster at breakfast, or a heater and tumble dryer together. That points to overload. Spread the load and see if it stops.

It trips immediately with a bang or a flash. That’s usually a short circuit, often in an appliance, a plug or a light fitting. Don’t reset it again until the item is unplugged and checked.

It trips after rain, after a leak, or when one particular appliance comes on. That points to earth leakage: water in an outside light or socket, or a heating element failing in a kettle, washing machine, oven or immersion heater.

It trips when a particular light is switched on. This often means a wiring fault between two circuits (see “borrowed neutrals” below), especially if it started after a new board.

Step-by-step: what to do when an RCBO trips

You can do these checks without tools and without removing any covers.

  1. Find the RCBO that’s down and read its label so you know which circuit it is (for example “kitchen sockets” or “upstairs lights”).
  2. Unplug everything on that circuit, and switch off any fixed appliances on it at their isolators.
  3. Reset the RCBO. Push it firmly all the way up.
    • If it won’t stay on with everything unplugged, the fault is in the fixed wiring or a hard-wired item. Stop and call an electrician.
  4. Plug things back in one at a time, waiting a minute between each. If it trips, the last item is the suspect. Try that item on a different circuit to confirm.
  5. If it’s a lighting circuit, switch the lights on one room at a time, and note which switch makes it trip.
Warning

Don’t keep resetting an RCBO that trips straight away, and never swap it for a bigger rating. A higher rating can let a cable overheat.

The faults we find most often

A faulty appliance or plug. Still the most common cause. Kettles, washing machines, dishwashers and ovens top the list.

Water in outside lights, sockets or fans. Check anything outdoors or below a recent leak.

Overloaded circuits. Older homes often have fewer circuits than modern life needs. Sometimes the fix is splitting a circuit in two. On a recent job in Wapping, for example, an EICR found a socket ring that needed attention. We split it into two radial circuits, each on its own 20A Type A RCBO. Read the Wapping case study.

Borrowed or shared neutrals. This is the classic one after a consumer unit upgrade. Every RCBO checks that the current going out on its live comes back on its own neutral. In some older homes, a light (often on the stairs or landing, or an extension) takes its live from one circuit and its neutral from another. On an old board with one shared RCD, nobody notices. Once each circuit has its own RCBO, the currents don’t match and the RCBO trips, often only when that one light is switched on. The fix is to trace and separate the circuits properly, not to remove the RCBO.

Neutral-to-earth faults. Where a neutral touches earth somewhere in the wiring, an RCBO can trip at random or when certain loads switch on. It needs testing with an insulation resistance tester to find.

Modern electronics on older-type RCBOs. Things like induction hobs, inverters, heat pumps and some chargers can leak a small amount of smooth DC current. Older Type AC devices aren’t designed for this. Current guidance calls for Type A RCBOs for most circuits, and some equipment needs more than that. An electrician can check which type you have and what your equipment needs.

A combined AFDD device. Some new boards use devices that combine an RCBO with arc fault detection (AFDD). These can trip on arcing from a loose connection or a damaged flex, and they often have an indicator light that shows why they tripped. On a job in Battersea, socket circuits on AFDD devices kept tripping on and off. We tested them fully and advised the customer to note what the indicator shows each time, so the cause can be pinned down. Read the Battersea case study.

A faulty RCBO. It’s possible, but it’s the least likely cause. We test the device before replacing it, so you’re not paying for a part that wasn’t the problem.

When to call an electrician straight away

  • the RCBO trips straight away, even with everything on that circuit unplugged
  • there was a bang, a flash, a burning smell or scorch marks
  • a socket, switch, plug or the board itself feels warm or makes a buzzing noise
  • the tripping started after a new fuse board, building work or a leak
  • the same RCBO keeps tripping every few days and you can’t find a pattern

What an electrician will do

We’ll ask when it trips and what was on, then test the circuit: insulation resistance (to find leakage to earth or between circuits), continuity, and a test of the RCBO itself. For borrowed neutral faults we isolate each circuit and test between them to prove where they’re joined. Once we’ve found it, we fix the fault and give you the test results.