Case Study: Socket Circuits Tripping on AFDDs in Battersea

This job was a fault-finding visit to a rented flat in Battersea, South West London (SW11). The tenants told us that both socket circuits had been tripping on and off, with no clear pattern. The landlord and tenants thought the boiler might be the cause. Our electrician went in early to test everything properly before anything was replaced.

What is an AFDD?

Both socket circuits in this flat are protected by AFDDs (arc fault detection devices). You may see them in newer or recently upgraded consumer units. They sit alongside the normal breaker and RCD protection and watch for the electrical “signature” of arcing: the small sparks you get from a loose connection, a damaged cable or a worn plug. Arcing can start a fire, so the AFDD switches the circuit off when it sees it.

AFDDs are a good safety upgrade, but because they react to arcing, they can also trip because of an appliance, a worn plug or a loose connection somewhere on the circuit. Finding out why they trip is the job.

What our electrician tested

  • Insulation resistance testing on the circuits. This checks that current isn’t leaking between the conductors or to earth through damaged insulation. The results came back clear.
  • End-to-end (continuity) tests on both rings. Both circuits showed a protective earth (r2) reading a little higher than expected, but not at a level we would expect to cause tripping.
  • Earth fault loop impedance (Zs) on both circuits, which was well within the expected values.
  • RCD trip times, which were also recorded.
  • The AFDDs themselves, which were showing no stored fault at the time of the visit.

What we found

On the day, the installation tested well. Intermittent faults are the hardest to find, because the circuit often behaves perfectly while the electrician is there.

  • Keep an eye on it, and when a circuit trips, note what the AFDD is showing before resetting it. Many AFDDs flash a code or light pattern that tells you what kind of fault they saw (for example arcing, overload or overvoltage).
  • Note what was running at the time: washing machine, heaters, chargers, the boiler.
  • When the fault is happening more often, book a return visit, so we can test while the problem is present and target the cause rather than guessing.

Tips if your own circuits keep tripping

  1. Write down when it happens and what was switched on.
  2. Unplug everything on that circuit, reset, then plug things back in one at a time. If one appliance trips it every time, that appliance is the likely culprit.
  3. Check plugs and extension leads for scorch marks, looseness or heat.
  4. Look at the device that tripped: is it the AFDD, the RCD or the breaker? They trip for different reasons.
  5. Don’t keep resetting a circuit that trips straight away. Leave it off and call an electrician.

Our guide why does my electric keep tripping? has more on this, and our electrical fault finding service covers visits like this one.

Electricians in Battersea and South West London

We work in Battersea, Clapham, Chelsea and across South West London for landlords, agents and homeowners, from fault finding and EICRs (from £175 + VAT) to consumer unit upgrades and full rewires. See our Chelsea page and all areas we cover.

Call 020 8227 0035 or request a quote.



Previous Post
Case Study: Ring Circuit Split and RCBO Upgrade in Wapping
Next Post
Case Study: Socket Failure and Electric Radiators in Hackney
Message us