This job was EICR remedial work in a rented flat in Wapping, East London (E1W). After the flat’s Electrical Installation Condition Report, the work needed was to sort out how the sockets and lights were split across the consumer unit. Here is what we did, why it matters, and what landlords and tenants can look out for.
What the job was
The brief from the EICR was clear:
- Split the socket ring into two radial circuits, each on its own 20 amp RCBO.
- Upgrade the lighting circuit’s breaker so it is correctly rated for the lighting it supplies.
Our electrician attended first thing in the morning, with the tenant still living in the flat, so the work was planned to keep the power off for as short a time as possible.
What we did
- Installed a 20 A Type A RCBO to supply the kitchen sockets and appliances.
- Installed a second 20 A Type A RCBO to supply the lounge and master bedroom sockets.
- Upgraded the lighting circuit from a 6 A MCB to a 10 A MCB.
- Tested the circuits and left the installation in a safe condition for continuous use.
All the remedial items were completed on the visit.
Why split a ring into two circuits?
In many flats, every socket in the home sits on one ring circuit. That ring has to carry the kitchen (kettle, oven, washing machine, dishwasher) as well as the living room and bedrooms. Splitting it into two separate circuits has some real benefits:
- Less load on each circuit. The kitchen, where most of the heavy appliances are, now has its own supply.
- A fault only takes out part of the flat. If an appliance trips its circuit, the bedroom and lounge sockets stay on.
- Each circuit has its own protection. An RCBO combines overload protection (like a normal breaker) with RCD protection (which cuts the power very fast if current leaks to earth, for example through a person). Having one per circuit means a single fault doesn’t trip everything.
- Type A RCBOs are designed to cope with the kind of leakage current modern appliances, chargers and electronics can produce, which is why they are now the usual choice for socket circuits.
Why change the lighting breaker?
A breaker has to be the right size for the circuit it protects. A 6 A breaker on a lighting circuit can be on the low side once a home has a lot of fittings, and can lead to nuisance tripping. The EICR asked for it to be 10 A, which we fitted, and the circuit was then tested.
What landlords should know
If your EICR comes back with C2 or FI codes, or recommends changes to how circuits are arranged and protected, the work needs to be done promptly. In England, landlords must fix C1, C2 and FI items within 28 days of the report (or sooner if the report says so) and give written confirmation to the tenant and, if asked, the council.
When we do remedial work, you get the work done, tested and certified, so you can show the installation is now satisfactory. Read more about the codes in our guide to EICR codes C1, C2, C3 and FI.
Signs your own flat might need the same work
- The whole flat loses power at the sockets when one appliance trips.
- The kitchen and bedrooms seem to be on the same breaker.
- Your consumer unit has one RCD covering lots of circuits, rather than one RCBO per circuit.
- Lights trip when you switch several on, or after new fittings are added.
If any of that sounds familiar, an EICR will show what needs doing, and a consumer unit upgrade is often the neatest fix.
Electricians in Wapping and Docklands
We work across Wapping, Canary Wharf and the Docklands (E1W and E14) every week, for landlords, letting agents, tenants and homeowners. See our Canary Wharf & Docklands page, our electrical services and EICRs for landlords. EICRs start from £175 + VAT.
Our engineers also cover the City of London, Islington, Finsbury Park and the rest of London and Essex from our base in Chigwell. Call 020 8227 0035 or request a quote.