Case Study: Socket Failure and Electric Radiators in Hackney

This job was in Hackney, East London (E9). The day before we visited, a fuse had blown with a loud bang and a visible spark, and the customer also wanted their wall-mounted electric radiators checked: some seemed underpowered, and the one by the window had started switching on and off by itself.

What our electrician found

  • A damaged socket was the source of the bang and spark. We replaced it with a new double socket.
  • Two of the radiators have 1,500 W heating elements, and both had failed. That explains why those radiators were not giving out the heat they should for their size.
  • A third radiator with a 2,000 W element was working, but its supply point needs a replacement metal-clad fused connection unit with a neon indicator, so you can see at a glance when it has power.
  • A new dedicated supply for the two affected radiators, so the heating is not sharing a circuit it may overload.
  • Replacement heating elements, correctly rated for the radiators.
  • The new fused connection unit with neon for the third radiator.
  • An optional consumer unit upgrade.

Each of these is quoted separately in writing, so the customer can decide what to do and when.

Why a bang and a spark should never be ignored

A loud bang from a socket usually means a short circuit: current taking a path it shouldn’t, often because of a loose or damaged connection, a damaged plug or water. The fuse or breaker did its job by cutting the power, but the cause still needs finding. Plugging back in and carrying on can lead to the same fault, or a fire.

If it happens to you:

  1. Switch off and unplug anything on that socket.
  2. Don’t use the socket again until it has been checked.
  3. Look for scorch marks, melting or a burning smell at the socket, plug or extension lead.
  4. Call an electrician, especially if the breaker trips again when you reset it.

Electric radiators: signs something is wrong

  • One radiator is cooler than others of a similar size.
  • It switches on and off when it shouldn’t, or the thermostat seems to be ignored.
  • The plug, spur or switch next to it gets warm.
  • Several heaters share one socket or extension lead.

Electric heaters draw a lot of current, so they need a supply that is sized for them. Our electricians can test the elements, check the wiring and spurs, and put in a dedicated circuit where needed.

Electricians in Hackney and East London

We work across Hackney, Islington, Finsbury Park, Wapping and Canary Wharf every week, as well as Essex. From fault finding and socket repairs to consumer unit upgrades, rewires and EICRs (from £175 + VAT), it’s all done by our own NICEIC-approved electricians. See our Islington page and all areas we cover.